Pipe Organ Blower Motor Problem
By Will Herzog

[ Bruce Newman wrote:

> When I energize the relay in the automatic starter, the motor turns
> on and comes up to speed but then turns off after a few seconds.
> The starter has two heater coils that seem to be heating up and
> throwing some kind of internal safety switch that shuts off the power.

Yes, those are heater coils that function to heat a tube that has
solder inside, which melts, allowing the overload to trip.

I worked at Allen-Bradley in the 1950s, testing a few thousand of them.
The coils vary depending upon the current limit desired, and are meant
to allow motor inrush high currents, yet prevent overloads.  So your
question is now whether the current of the limiters, or to the motor is
too high.  It may be too high if the motor is attempting to run on the
starter winding instead of the run winding.

Will Herzog



(Message sent Sun, 29 Apr 2007 21:50:13 -0500 , from time zone -0500.)

Key Words in Subject:  Blower, Motor, Organ, Pipe, Problem

Related by Subject:
2007.05.02.07 - Pipe Organ Blower Motor Problem
from Jim Crank
2007.05.02.08 - Pipe Organ Blower Motor Problem Solved
from Bruce Newman
2007.05.01.02 - Pipe Organ Blower Motor Problem
from Bruce Newman
2007.04.30.07 - Pipe Organ Blower Motor Problem
from Larry Doe
2007.04.30.08 - Pipe Organ Blower Motor Problem
from John Nolte
2007.04.30.09 - Pipe Organ Blower Motor Problem
from Robbie Rhodes
2007.04.29.07 (This article) - Pipe Organ Blower Motor Problem
from Will Herzog
2007.04.29.08 - Pipe Organ Blower Motor Problem
from Mike Knudsen
2007.04.29.09 - Pipe Organ Blower Motor Problem
from Bill Finch
2007.04.28.05 - Pipe Organ Blower Motor Problem
from Bruce Newman